UPS-PC-652A

Question
UPS switches off automatically after a very short time, but the battery indicator still shows (almost) full battery.
Answer
Every UPS has a certain maximum power output (W), but also a minimum required load. In order to work correclty, the connected load should be at least 5% of the maximum capacity of the UPS. For example, a 700 W UPS needs at least a connected load of 35 W to work. Otherwise it will shut itself down automatically as a safety measure to preserve the batteries. Also when the connected load is higher than the maximum capacity of the UPS, the device will shut down.

UPS-PC-1202AP

Question
UPS switches off automatically after a very short time, but the battery indicator still shows (almost) full battery.
Answer
Every UPS has a certain maximum power output (W), but also a minimum required load. In order to work correclty, the connected load should be at least 5% of the maximum capacity of the UPS. For example, a 700 W UPS needs at least a connected load of 35 W to work. Otherwise it will shut itself down automatically as a safety measure to preserve the batteries. Also when the connected load is higher than the maximum capacity of the UPS, the device will shut down.

UPS-PC-850AP

Question
UPS switches off automatically after a very short time, but the battery indicator still shows (almost) full battery.
Answer
Every UPS has a certain maximum power output (W), but also a minimum required load. In order to work correclty, the connected load should be at least 5% of the maximum capacity of the UPS. For example, a 700 W UPS needs at least a connected load of 35 W to work. Otherwise it will shut itself down automatically as a safety measure to preserve the batteries. Also when the connected load is higher than the maximum capacity of the UPS, the device will shut down. Question
UPS switches off automatically after a very short time, but the battery indicator still shows (almost) full battery.
Answer
Every UPS has a certain maximum power output (W), but also a minimum required load. In order to work correclty, the connected load should be at least 5% of the maximum capacity of the UPS. For example, a 700 W UPS needs at least a connected load of 35 W to work. Otherwise it will shut itself down automatically as a safety measure to preserve the batteries. Also when the connected load is higher than the maximum capacity of the UPS, the device will shut down.

BC-USB-02

Question
USB output port for practical powerbank function (5V / 2A) But no info with batteries type supports 5V/2A?
Answer
This charger can charging powerbank,need put into 3.7V lithium-ion rechargable batteries with 5V output.(put into li-ion rechargeable battery, activate USB output,if there is no load,it will into automatic sleep mode) Question
This charger supports 18650 Soshine LiFePO4 1800 mAh 3.2V protected batteries?
Answer
This charger not support with 3.2V LiFePO4 battery,only can use for 3.7V lithium-ion rechargeable battery,1.2V NiMH rechargeable battery and 1.2V NiCd rechargeable battery. Question
What fast recharge protocols does USB-C support for charging the batteries themselves?
Answer
Input for Type C:5V/2A 9V/2A 12V/1.5V Output for fast charging: 4.2V 0.75A*4 1.5A*2 3.0A*1,need put batteries in the first slot or in the fourth slot Question
What type of batteries does the 5V/2A USB PowerBank need Ni-MH / Ni-CD / Li-ion (form-factor)?
Answer
3.7V Li-ion recharegable batteries
Display 12, 24, 48, all records per page